You are currently exploring our in-stock options for part number TQC2130WL with the NSN 5925007245539. This product is listed with the description “Circuit Breaker” and is manufactured by General Electric Company. If you are looking to purchase this part, we encourage you to complete and submit the RFQ form below with as much information as you can provide, such as your desired quantity, budget, shipping time frame, and more. Within 15 minutes of receiving and reviewing your submission, one of our experts will reach out with a quote that is tailored to your needs.
Note : We Will Not Share Your Information To Any Third Parties.
We supply all relevant information alongside the listings on our website, that way you know you are always getting the exact item you require. For example, part number TQC2130WL is listed alongside the NSN 5925-00-724-5539 and belongs to the FSC 5925 Circuit Breakers. Additionally, it is also under the CAGE Code 03497, which is assigned to General Electric Company. At Aerospace Procurement, you can trust that each product in our inventory is up to industry standards, as we are committed to various quality assurance practices. For example, we uphold a strict NO CHINA SOURCING pledge to ensure that each part is shipped out alongside its manufacturer trace documentation and qualifying certifications. These practices and more allow us to operate with AS9120B, ISO 9001:2015, and FAA AC 00-56B accreditation. Get in contact with us today to see how we can make the procurement process for part number TQC2130WL seamless.
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-00-724-5539 Item PartTypeName: CIRCUIT BREAKER | 5925 | 007245539 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | A | 0 | ||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
TQ2130WL | 5 | 9 | 5 |
MRC | Criteria | Characteristic |
---|---|---|
ADAT | BODY WIDTH | 2.000 INCHES MAXIMUM |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.000 INCHES NOMINAL |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 TERMINAL |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 140.0 ALL LOCATIONS |
CPRX | ACTUATOR POSITION DESIGNATION | AT EACH POLE |
CPRY | EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE AND TWO LINKED |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 18.000 MINIMUM AT 200 PCT AND 125.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | GENERAL PURPOSE |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 50.0 DEG CELSIUS MAXIMUM ALL LOCATIONS |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
AAQL | BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
ADAQ | BODY LENGTH | 3.875 INCHES NOMINAL |
ADAU | BODY HEIGHT | 2.359 INCHES NOMINAL |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
AJEC | BOSS HEIGHT | 0.187 INCHES NOMINAL |
AKPX | POLE QUANTITY | 2 |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 30.0 AMPERES AC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 10000.0 AC ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | THERMAL ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 2 TOGGLE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CWJK | CASE MATERIAL | PLASTIC |
TTQY | TERMINAL TYPE AND QUANTITY | 2 CLIP AND 2 COMPRESSION |