You are currently exploring our in-stock options for part number CM-21A with the NSN 6665015302725. This product is listed with the description “Alarm Gas Automatic” and is manufactured by Aerion Technologies Inc. If you are looking to purchase this part, we encourage you to complete and submit the RFQ form below with as much information as you can provide, such as your desired quantity, budget, shipping time frame, and more. Within 15 minutes of receiving and reviewing your submission, one of our experts will reach out with a quote that is tailored to your needs.
Note : We Will Not Share Your Information To Any Third Parties.
We supply all relevant information alongside the listings on our website, that way you know you are always getting the exact item you require. For example, part number CM-21A is listed alongside the NSN 6665-01-530-2725 and belongs to the FSC 6665 Hazard Detecting Instruments And Apparatus. Additionally, it is also under the CAGE Code 2Y359, which is assigned to Aerion Technologies Inc. At Aerospace Procurement, you can trust that each product in our inventory is up to industry standards, as we are committed to various quality assurance practices. For example, we uphold a strict NO CHINA SOURCING pledge to ensure that each part is shipped out alongside its manufacturer trace documentation and qualifying certifications. These practices and more allow us to operate with AS9120B, ISO 9001:2015, and FAA AC 00-56B accreditation. Get in contact with us today to see how we can make the procurement process for part number CM-21A seamless.
MRC | Criteria | Characteristic |
---|---|---|
APGF | DESIGN TYPE | NONTRIPOD MOUNTING |
AFJK | III CUBIC MEASURE | 38.250 CUBIC INCHES |
SUPP | III SUPPLEMENTARY FEATURES | DIMENTIONS ARE 4.5 X 4 X 2.125 INCHES. ITEM SHOULD BE MOUNTED 4 TO 5 FEET ABOVE FLOOR LEVEL. |
FEAT | SPECIAL FEATURES | CM-21A ACTIVATES FAN RELAY AT 35 PPM OF CO AVERAGED OVER 5 MINUTES. (25 PPM IS SELECTABLE) ALARM RELAY WILL BE ACTIVATED AT 100 PPM OF CO AFTER 30 MINTUTES OR 200 PPM AFTER 10 MINUTES. 5 AMP SPDT FAN RELAY CONTROLS STARTERS OF EXHAUST FANS. A 0.5 AMP N.O. ALARM RELAY CONNECTS TO WARNING DEVICES OR CONTROL PANELS. |
BRQN | MEDIA DETECTED | CARBON MONOXIDE |
CXCY | III PART NAME ASSIGNED BY CONTROLLING AGENCY | CARBON MONOXIDE DETECTOR AND CONTROLLER |
ALBY | USAGE DESIGN | INDUSTRIAL |
ALXZ | SPECIFIC USAGE DESIGN | DESIGNED FOR CO DETECTION AND AUTOMATED EXHAUST FAN CONTROL IN AUTOMOTIVE MAINTENANCE FACILITES, ENCLOSED PARKING GARAGES, WAREHOUSES WITH FORKLIFTS, ETC. |
AMKD | INDICATOR TYPE | RED LIGHT AND HORN |